Electrical Wire Test

Old 05-16-2010, 04:49 PM
  #1  
Senior Member
Thread Starter
 
Join Date: Jun 2004
Posts: 2,298
Received 44 Likes on 29 Posts
Default Electrical Wire Test

How do we check an under ground 10-2 wire that is 200ft long to see if there is a break--fault? This in on a irrigation system and when we disconnected the wires at the breaker near the pump and left them connected to the main panel, the breaker throws. I really don't want to have to dig and replace 200ft of wire.
Thanks,
Old 05-16-2010, 04:56 PM
  #2  
Senior Member
 
Join Date: Sep 2009
Location: Mobile, AL
Posts: 668
Likes: 0
Received 2 Likes on 1 Post
Default

disconnect both ends of the wire. Wire the black and white together on one end and do continuity test on the other end with a multimeter. There should be a setting on the multimeter that buzzes when the two leads are touched.

Last edited by BigPumper; 05-16-2010 at 05:13 PM.
Old 05-16-2010, 05:05 PM
  #3  
Senior Member
Thread Starter
 
Join Date: Jun 2004
Posts: 2,298
Received 44 Likes on 29 Posts
Default

Thanks, I am familiar with electrical wiring but not using meters and trouble shooting unless it is trail and error.
Old 05-16-2010, 06:17 PM
  #4  
Senior Member
 
Join Date: Aug 2009
Posts: 2,893
Likes: 0
Received 447 Likes on 184 Posts
Default

Big pumper nailed it. Just make sure you unhook it from the main circut breaker first.
Old 05-16-2010, 06:24 PM
  #5  
Senior Member
 
Join Date: Sep 2009
Location: Mobile, AL
Posts: 668
Likes: 0
Received 2 Likes on 1 Post
Default

But if the breaker is popping when you turn the circuit on, you might want to try and do the continuity test with the wires just disconnected.

What does the circuit run? Try disconnecting it from whatever it runs and then turn it on..... If the breaker pops then, the wire is bad. Dont forget to wire nut the end of the wires when you disconnect it from whatever it runs.
Old 05-16-2010, 07:31 PM
  #6  
Senior Member
 
Join Date: Mar 2007
Location: So. Calif
Posts: 494
Likes: 0
Received 0 Likes on 0 Posts
Default

If you need to locate the fault , you need a time delay reflectometer--and someone who has one and knows how to use it.
Old 05-17-2010, 04:25 AM
  #7  
Senior MemberCaptains Club Member
 
Join Date: Nov 2002
Location: Groton, CT. USA
Posts: 2,576
Likes: 0
Received 33 Likes on 22 Posts
Default

Do it right and get hold of a megger
.....http://www.testequipmentdepot.com/me...t200series.htm
Old 05-17-2010, 05:09 AM
  #8  
Senior Member
 
Join Date: Jun 2009
Location: Lake Murray, SC
Posts: 4,252
Received 206 Likes on 114 Posts
Default

You could also try disconnecting the wire from the breaker and see if it still throws. Breakers can go bad and are easy to replace.
Old 05-17-2010, 06:11 AM
  #9  
Senior MemberCaptains Club Member
 
Join Date: Dec 2007
Posts: 15,737
Likes: 0
Received 653 Likes on 359 Posts
Default

If continuity tests to zero, or close, then wiring is OK.

As jrolin1 said, you could switch the breaker with a known other breaker of the same rating and see if things stay the same. That means that your breaker is OK.

Your next test is the pump motor for an overly high starting draw; indicative of a failing motor.

If you aren't familiar with a volt-meter, no worries. Go to Radio Shack or electrical supply house or big box store. Any of their salesmen will be able to spend the two minutes it takes to get you comfortable with using it's most common features (12V, 120V, and continuity testing)
Old 05-17-2010, 01:44 PM
  #10  
Senior Member
Thread Starter
 
Join Date: Jun 2004
Posts: 2,298
Received 44 Likes on 29 Posts
Default

Step one we replaced the breaker at the main panel with no positive results and then the one at the pump location. Same result, thrown breaker at the main panel. Disconnected the wire from the relay and the breaker did not throw. Took the wire loose from the breaker panel near the pump, hooked it back up at the main panel and it threw again. Took it loose at the main panel and hooked a dummy wire up and it did not throw. Re installed the wire at the main panel and then took the wire loose at the breaker panel near the pump and it threw. This lead me to believe the main wire under ground is bad. Just hate to spend $250.00 and dig another trench.
Thanks for the replies.
Old 05-17-2010, 01:49 PM
  #11  
Senior Member
 
Join Date: May 2009
Posts: 1,660
Likes: 0
Received 43 Likes on 27 Posts
Default

If you disconnected the equipment out in the field so that nothing is hooked to the wires and the breaker still trips your going to have to replace the wire in the ground.
Old 05-17-2010, 05:44 PM
  #12  
Senior Member
Thread Starter
 
Join Date: Jun 2004
Posts: 2,298
Received 44 Likes on 29 Posts
Default

That's what I thought. Sometimes you just don't want to hear the truth, you know what I mean? $250.00 for wire and a ditch to dig.

Thanks
Old 05-17-2010, 06:11 PM
  #13  
Senior Member
 
Join Date: Jun 2009
Location: Lake Murray, SC
Posts: 4,252
Received 206 Likes on 114 Posts
Default

Just finished doing that yesterday for underground speaker wire and low voltage lighting. Not much fun. good luck.
Old 05-17-2010, 07:13 PM
  #14  
Senior MemberCaptains Club Member
 
Garett's Avatar
 
Join Date: Feb 2003
Posts: 24,667
Likes: 0
Received 1,130 Likes on 634 Posts
Default

If the wire is underground shouldn't it be in a conduit? If so, what kind, what size? I would think 1" PVC would be the min. Why can't you just attach your replacement wire to the old wire and pull the new wire through......saving you the dig? If you have to buy some fishing lube to lube up the inside of the conduit as you pull your new wire through.
Old 05-17-2010, 08:43 PM
  #15  
Senior Member
 
Join Date: Jan 2010
Location: Vancouver Island
Posts: 346
Likes: 0
Received 0 Likes on 0 Posts
Default

It could be direct burial, non metalic, wet, underground (NMWU). Repair with PVC conduit might be a good idea with single conductors.(R90)
Old 05-19-2010, 09:06 PM
  #16  
Senior MemberCaptains Club MemberPLEDGER
 
Join Date: Mar 2005
Location: Whitesboro, texas
Posts: 8,055
Likes: 0
Received 13 Likes on 11 Posts
Default

FYI, I don't care what type of wire you use , PUT IT IN CONDUIT , We have customers that have VERY electric bills because of Direct bury wire mixed with MOLES AND GOPHERS .
Old 05-19-2010, 09:32 PM
  #17  
Senior MemberCaptains Club Member
 
Join Date: Oct 2003
Location: Seattle, Wa
Posts: 1,269
Likes: 0
Received 3 Likes on 1 Post
Default

Listen to Welder!
Old 05-20-2010, 01:05 PM
  #18  
Senior Member
 
Join Date: Mar 2009
Location: Central Jersey
Posts: 109
Likes: 0
Received 0 Likes on 0 Posts
Default

This is what you need to mark out then pinpoint the fault location. Of course buying the unit is more expensive then paying to have the trench reopened. Do yourself a favor and place the new wires in conduit, it's cheap and you can always pull a new wire through it if you have problems in the future.


http://multimedia.3m.com/mws/mediawe...6EVs6E666666--
Old 05-20-2010, 01:25 PM
  #19  
Senior MemberCaptains Club Member
 
Join Date: Sep 2002
Location: On the wild side !!
Posts: 5,708
Received 52 Likes on 31 Posts
Default

You can direct bury 10-2 UF but I would install it in gray/ elect PVC.

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are On
Refbacks are Off


Thread Tools
Search this Thread

Contact Us - Archive - Advertising - Cookie Policy - Privacy Statement - Terms of Service - Do Not Sell My Personal Information -

Copyright © 2018 MH Sub I, LLC dba Internet Brands. All rights reserved. Use of this site indicates your consent to the Terms of Use.